WINTERPORT WATER DISTRICT
CROSS-CONNECTION CONTROL POLICY AND PROCEDURES
Adopted September 18, 2000

 

Table of Contents

I Introduction
II Control Method - Containment
III Implementation Policy
   
  APPENDIX A - DEFINITIONS

 

 

 

 

 

 


I. INTRODUCTION 
Table of Contents

This document sets forth the District’s policy and procedures for implementation of its Cross-Connection Control Program.

II. CONTROL METHOD – CONTAINMENT 
Table of Contents

A. General

There has been an ongoing debate concerning the method of cross-connection control that should be implemented by water utilities – containment or fixture isolation. In addition, there have been increasing efforts by people specializing in cross-connection control (primarily certification organizations and testers) to pressure public water suppliers to adopt fixture isolation as the preferred method for implementing cross-connection control. The District employs the containment method.

Briefly, the containment method is implemented by installing a backflow preventer at the service connection to prevent used water from re-entering the public water system. Fixture isolation prevents contamination of the public water system and the customer’s internal plumbing system by requiring installation of a backflow preventer at all plumbing fixtures within the building. Although cross-connection professionals have stated this philosophy of cross-connection control as a requirement, it has not been established by regulation. This philosophy is based primarily on two arguments:

1. The lead and copper rule has established precedent by assigning responsibility for water quality with respect to corrosivity at the customer’s tap to the supplier. If the supplier is also responsible to insure that all water quality standards are met at the tap, and internal cross-connections can degrade water quality, then the utility is also responsible to protect the internal plumbing system.

2. Customers are unfamiliar with cross-connections, their hazards, and methods of control. Therefore, they cannot be relied upon to insure that all plumbing fixtures are protected from cross-connections. The supplier, however, is knowledgeable and its position and resources make it suited to serving as the primary enforcement agency for protection of internal fixtures. In addition, the State Cross-Connection Rules give authority to the supplier to enter private property to inspect the customer’s water supply system. Therefore, the utility should be responsible for protecting the customer’s water supply system.

A discussion of industry practice and governing regulations follows.

B. AWWA M14

American Water Works Association Manual of Water Supply Practices M14, Recommended Practice for Backflow Prevention and Cross-Connection Control”, “has been designed as a guide toward uniformity for waterworks employees, plumbers, and others involved in the detection and elimination of unprotected cross-connection” (Section 1.1). Section 1.2 of the manual outlines the responsibilities of the various parties involved in cross-connection control.

Respective responsibilities are excerpted below, with comment:

Water User (Owner or Customer):
“The water user has the primary responsibility to keep contaminants out of the potable water system(s). This responsibility begins at the user connection and includes any and all water distribution piping on the premises.” In Maine, the user connection is defined as the outlet end of the meter. “Water system(s)” is taken to mean the public water system and the customer’s internal plumbing system.

Water Supplier:
“The water supplier has the responsibility to prevent contamination of the public water system from backflow. This responsibility begins at the source and includes the entire distribution system and ends at the user connection.” Further it states, “In some jurisdictions, such as Washington state and Massachusetts, legislation requires that the water supplier conduct surveys of internal potable water systems and implement programs to afford protection for both the public water supply and the individuals on the premises”.

Health Agency
“The health agency also has the responsibility for promulgating and enforcing laws, rules, regulations, and policies to be ollowed in controlling cross-connections. The agency has the responsibility to ensure that internal protection is provided and adequate backflowprevention programs are maintained.” In Maine, the health agency is the Department of Human Services, Bureau of Health. DHS promulgates “Rules Relating to Drinking Water” (Chapter 231), “Cross-Connection Rules” (Chapter 226), and “State of Maine Internal Plumbing Rules” (Chapter 238).

Plumbing Official
“The plumbing official has the responsibility for the enforcement of plumbing regulations concerned with preventing cross-connections.” In Maine, the Local Plumbing Inspector is the designated plumbing official.

C. USEPA Cross-Connection Control Manual

The “USEPA Cross-Connection Control Manual” was last revised in 1989 and is intended to serve as a technical reference in conducting cross-connection control programs. In Chapter 6, Administration of a Cross-Connection Program, the benefits and drawbacks of containment and fixture isolation are discussed. The manual states that the fixture isolation approach in large systems “is a virtual impossibility to achieve and to police”. It further acknowledges that “internal plumbing cross-connection control survey work is generally foreign to the average water purveyor”. Also, “While it is admirable for the water purveyor to accept and perform survey work, he should be aware that he runs the risk of additional liability in an area that may be in conflict with plumbing inspectors, maintenance personnel and other public health officials.” Further guidance is given with respect to survey work. “If ‘containment’ is the prime objective of the survey, then only sufficient time need be spent in the facility to determine the degree of hazard inherent within the facility or operation.”

D. USC Foundation for Cross-Connection Control and Hydraulic Research

USC conducts research, sets standards, and tests and approves backflow preventers. In addition, it publishes the “Manual of Cross-Connection Control” to provide responsible parties with information and suggested practices to implement effective cross-connection control programs. Section 3 of the manual lists the
responsibilities of the various parties. The manual is in agreement with the responsibilities as assigned by AWWA. The plumbing official’s responsibility is explicitly stated:

3.3 Responsibility: Plumbing Official
“The plumbing official’s responsibility begins at the point of service (the downstream side of the meter) and carries throughout the entire length of the customer’s water system.”

E. State Cross-Connection Rules

The State of Maine Cross-Connection Rules (CMR 10-144, Chapter 226) does not assign responsibilities as explicitly as the preceding manuals. It simply states in Section 2:

A. The supplier shall not permit any cross-connection at any point within its system unless approved pursuant to a permit specifically issued for the cross-connection.

B. The owner shall be responsible for insuring the proper operation and maintenance of an anti-backflow device and the periodic testing of the device.

F. State Plumbing Code

The State of Maine Internal Plumbing Rules (CMR 10-144, Chapter 238) also addresses cross-connections. No specific responsibility is assigned, except that the local plumbing inspector has the responsibility of preventing cross-connections from being designed or built into buildings within their jurisdiction.

G. Maine Public Utilities Commission

Maine PUC does not have any rules pertaining to cross-connection control. Nevertheless, PUC considered the issue in re: Robert E. Baldacci, Sr., et al., v. Bangor Water District, Docket No. 88-251. The case considered whether or not the Bangor Water District’s cross-connection control program was reasonable in that it required all service connections to have a backflow preventer whether or not an actual cross-connection existed. The staff recommendation for the case discussed the containment method, and stated that, “The rationale behind the containment method also implicitly recognizes that anyone in Maine can do their own plumbing. Because unlicensed and perhaps unqualified people are permitted to install and work on their own plumbing, cross-connections may be inadvertently present. Furthermore, as houses change owners over the years, plumbing may also change, thereby making it difficult for a public water supplier, such as the District, to keep track of individual cross-connections”. PUC agreed with the staff recommendation and dismissed the complaint, finding that the District’s cross-connection control program was reasonable.


H. Conclusions

The rationale for assignment of responsibility of water quality protection to the tap by the supplieris derived from the lead and copper rule, which requires that the water be non corrosive at the tap. Some people conclude that since this is required, the supplier is also responsible for all water quality at the tap. Nevertheless, the rule contains no provisions concerning other contaminants, and nowhere mentions cross-connections. The 1986 Safe Drinking Water Act Amendments included the following language within the definition for Maximum Contaminant Level: “Contaminants added to the water under circumstances controlled by the user, except those resulting from corrosion of piping and plumbing caused by water quality, are excluded from this definition.” (CFR 40, Paragraph 141.2, Section C). Therefore, there is no reasonable basis to conclude that the supplier is responsible for all water quality parameters at the tap.

The argument that the supplier’s position and resources establish responsibility for water quality at the tap similarly has no basis. It assumes that utility personnel are as knowledgeable as licensed plumbers and ignores the responsibilities assigned to plumbers and the local plumbing inspectors in the Internal Plumbing Rules. Water utilities do not routinely employ licensed plumbers, nor is it reasonable to expect that they should since it is not necessary for the operation of a public water supply. The point is made in Baldacci that the supplier cannot be expected to maintain control over the internal plumbing of all of its customers. This is also acknowledged in the EPA Cross-Connection Control Manual.

The organizations and documents cited above clearly show that the responsibility of the District is to insure that connections to the public water system are protected to prevent contamination. The State assigns responsibility for internal protection to the water user and the local plumbing inspector via the Internal Plumbing Rules. The ability of the District to exercise and maintain control over all customers’ plumbing systems is practically impossible and the potential liability inherent with such a program is incalculable. On the basis of these considerations, therefore, the District shall continue to use the containment method of cross-connection control.

III. IMPLEMENTATION POLICY 
Table of Contents

A. Policy

The District recognizes that the containment method provides protection of the public water system from existing or potential cross-connections. Further, actual cross-connections may not exist and, therefore, cross-connection control would theoretically be unnecessary. Nevertheless, undetected cross-connections may exist, and uncontrolled plumbing changes may be made subsequent to inspection and without the District’s knowledge. These conditions may result in a cross-connection, either knowingly or unknowingly, and pose a public health threat. Therefore, in consideration of the need to protect the public water supply from actual and potential cross-connections, it shall be the policy of the District to implement cross-connection control by the containment method.

B. Responsibilities

1. The General Superintendent/Operator shall have overall responsibility to insure that the District’s Cross-Connection Control Program is implemented.

2. The District Operator shall be designated as the Cross-Connection Control Officer, and shall insure that the procedures set forth in this policy and procedures are implemented. The District Operator shall determine the degree of hazard present at all customer facilities and shall specify the type of backflow preventer to be installed.

3. The District Operator Technician shall be responsible for daily operations related to the Cross-Connection Control Program, including preparation of all correspondence and record keeping.

4. The General Business Manager shall be responsible to insure that no new water meter or replacement meter is installed unless a backflow preventer is in place.

C. Compliance Schedule

1. Industrial Customers:
The District recognizes that industrial operations using public water in production processes represent a potential public health threat by the nature of their operations. The District shall therefore inspect and require installation of a backflow preventer commensurate with the potential degree of hazard present for all industrial customers by January 1, 2001.

All industrial customers shall be re-inspected every five years to verify the degree of hazard assigned.

2. Commercial and Governmental Customers:
The District recognizes that commercial and governmental concerns may use public water under conditions that would cause potential nuisance or public health threats if a backflow incident were to occur. The District shall therefore inspect and require installation of a backflow preventer commensurate with the potential degree of hazard present for all commercial and governmental customers by January 1, 2003.

All commercial and governmental customers shall be re-inspected every five years to verify the degree of hazard assigned.

3. Residential Customers:
District rules and regulations require that all customers shall install a back flow prevention device when their meter is replaced, their water service is renewed and when any change in the customers internal plumbing occurs. This requirement shall be maintained for all existing residential customers. All new customers shall install a back flow prevention device on the outlet side of the water meter before service is established.

D. Procedures for Implementation

1. General:

a. American Water Works Association Manual M14, “Recommended Practice for Backflow Prevention and Cross-Connection Control”, shall serve as the basis for practices concerning all aspects of the District’s Cross-Connection Control Program relating to administration, hazard classification, methods of control, and fire protection system requirements.

b. All correspondence giving notice for inspection of premises, inspection results, compliance requirements, and test requirements shall be sent by registered mail, return receipt requested. All time periods specified for giving notices and compliance requirements shall be calendar days unless otherwise specified.

2. New Customers:

a. All new customers shall install an approved back flow prevention device on the outlet side of the water meter.

1.) All residential customers shall install at a minimum a dual check valve type backflow preventer.

2.) All non-residential customers shall install a device commensurate with the degree of hazard.

b. Customers shall be informed of the device requirements and receive an application for a cross-connection permit, if required, when application for service is made.

c. Water service shall not be established until a backflow preventer has been installed and, where required, has been tested and a permit application has been received by the District.

3. Existing Non-Residential Customers

a. All non-residential customers’ premises shall be inspected to determine the potential degree of hazard present. Until inspection of premises is completed, all non-residential customers shall be presumed to be Class II or higher hazards.

b. Notification of inspection of premises shall be done in accordance with the District’s Cross-Connection Control Program.

c. District personnel or a District contractor shall perform inspections.

d. Notification shall be provided to non-residential customers at least 14 days in advance that the District intends to inspect their premises.

e. Within seven days of the inspection, notice shall be sent to the customer to inform them of the degree of hazard assigned and the type of backflow preventer required.

f. The customer shall be given at least 30 days to comply with the requirements of the Cross-Connection Control Program.

g. The facility shall be re-inspected not more than 45 days after notification to verify the presence of a backflow preventer.

h. If compliance is not achieved, the customer shall be given an additional 10 days to comply.

i. If the customer fails to comply following the second notice, water service to the premises shall be terminated in
accordance with District Rules and Regulations and PUC rules.

4. Degree of Hazard

Different types of cross-connections constitute different degrees of hazard which are classified as follows, listed with the approved types of devices:

A. Class I - If backfiow were to occur, the resulting health significance would be limited to minor changes in the esthetic quality such as taste odor, or color. The foreign substance must be non-toxic and non-bacterial in nature and have no significant health effect. Allowed devices are air gap, non-pressure type vacuum breaker, pressure type vacuum breaker, testable double check valve assembly, or reduced pressure principle device.

B. Class 2 - If backflow were to occur, the resulting effect on the water supply would be significant chance in esthetic qualities. The foreign substance must be non-toxic and non-bacterial in nature. Allowed devices are Air gap, pressure type vacuum breaker, testable double check valve assembly, or reduced pressure principle device.

C. Class 3 - If backflow were to occur, the resulting effect on the water supply could cause illness or death if consumed by humans. The foreign substance may be toxic to humans either from a chemical, bacteriological or radiological standpoint and may result from either long or short-term exposure. Allowed devices are air gap or reduced pressure principle device.

5. Existing Residential and Class I Hazard Non-Residential Customers

a. All residential customers shall be considered Class I hazards, and shall be protected at a minimum by a dual check valve backflow preventer.

b. Permits and annual testing for Class I devices will not be required.

c. All new residential and Class I hazard non-residential customers shall install at a minimum a dual check valve backflow preventer.

d. All residential customers shall be considered Class I Hazards, and shall be protected at a minimum by a dual check valve backflow prevention device installed on the outlet side of the water meter.

e. For customers requesting that their service be renewed, or any service scheduled to be renewed as part of any main or service replacement program, the District shall provide 30 days notice prior to commencement of the work that the customer shall install a backflow preventer.

f. The District shall verify that the backflow preventer has been installed prior to commencement of the work. If a customer has failed to install a backflow preventer, a second notice shall be sent and the customer shall be given an additional ten days to comply.

g. If the customer fails to comply, water service shall be terminated in accordance with District Rules and Regulations and PUC rules.

h. For all customers scheduled to have their meter replaced either by customer request or District initiative, notification that a backflow preventer shall be installed shall be given as outlined in parts (e) through (g) above.

6. Testing

a. Testing shall be done in accordance with the District’s Cross-Connection Control Program.

b. The District, a District contractor, the customer, or the customer’s contractor may do testing.

c. The tester shall be recognized as competent to test backflow preventers by holding a valid certificate from the New England Water Works Association or American Backflow Prevention Association. The District will consider other certification programs on a case-by-case basis. The District shall maintain a list of certified testers acceptable to the District for referral to customers.

d. Testable (Class II and III) devices shall be tested upon installation and annually thereafter.

e. All tests shall be scheduled to be completed by September 30.

f. At least 10 but not more than 20 days after the test period closes, the District will send written notice to customers who failed to test their backflow preventer. The customer shall be given 30 days to complete the test.

g. If a customer fails to test their device following the first notice, a second written notice will be given. The customer shall be given an additional 10 days to complete the test.

h. If a customer fails to test their device after the second notice, water service shall be terminated in accordance with
District Rules and Regulations and PUC rules.

i. The customer shall notify the District within 24 hours of any device that fails a test, and shall endeavor to repair the device as soon as possible. If the device fails after repairs have been made, the District may require that the device be replaced. If an imminent health hazard exists, the District may terminate service to the premises immediately.

E. Related Issues

1. Responsibility with respect to internal cross-connections:
The District recognizes that cross-connections may exist in the customer’s water supply system, and that the containment method does not afford protection to internal plumbing fixtures. Therefore, the District shall advise the customer in all correspondence that the customer should retain a qualified professional to insure that internal cross-connections are adequately protected from backflow.

2. Responsibility with respect to thermal expansion:
The District recognizes that installation of a backflow preventer may prevent water that expands due to heating from moving back into the public water supply system, and that resulting pressure increases could cause safety and relief valves to operate, or equipment or piping to fail. Therefore, the District shall notify all customers required to install a backflow preventer that they should retain the services of a qualified professional to insure that their water supply system is adequately protected from the effects of thermal expansion.

3. Education:
The District recognizes that customers may not be knowledgeable concerning cross-connection control. Therefore, the District shall periodically inform customers of the general concepts of cross-connection control and the District’s program requirements through mailings of brochures and other educational materials. In addition, the District shall maintain a file of materials that may be sent to customers upon request for more detailed or site-specific information.

F. Program Review

The District Cross-Connection Control Program shall be reviewed and amended as required in January every two years, beginning in 2002. Revised programs shall be submitted to the Department of Human Services for review and approval.

G. Record-keeping Requirements

1. Non-permit devices:
The District shall maintain records of all Class I devices.

2. Permitted devices:
The District shall maintain installation, test, and repair records of all Class II and III devices.

 

 

APPENDIX A
DEFINITIONS





A. Antifreeze compounds: Any liquid, chemical or other material used as an antifreeze or heat-exchange medium. Use of antifreeze compounds is limited to propylene glycol and food-safe glycerin; ethylene glycol (automobile antifreeze) is prohibited.

B. Backflow: The flow of water or other foreign liquids, gases, or other substances or materials of any kind in any form into the distribution system of a public water supply from any source other than the intended.

C. Backflow Prevention Device: A device to prevent backflow.

A. Air Gap: A physical separation sufficient to prevent backflow between the free-flowing discharge end of the potable water system and any other system.

B. Atmospheric Vacuum Breaker: A device which prevents back-siphonage by creating an atmospheric vent where there is either a negative pressure or sub-atmospheric pressure in a water system.

C. Backflow Prevention Device with Intermediate Atmospheric Vent: A device having two check valves separated by an atmospheric vent.

D. Double Check Valve: A device having two independently acting, approved check valves that are internally loaded with two resilient seated shut-off valves and test cocks for periodic testing. Referred to as a "testable" device by the District; requires permitting by the Department.

E. Dual check valve: A device having two independently acting, approved check valves. Used primarily in residential and low hazard non-residential situations. Referred to as a "non-testable" device by the District; does not require permitting by the Department.

F. Hose Bib Vacuum Breaker: A device which is permanently attached to a hose bib and which acts as an atmospheric breaker.

G. Pressure Vacuum Breaker: A device containing a spring-loaded check valve and a spring-loaded atmospheric vent which opens when pressure approaches atmospheric. It contains valves and fittings which allow the device to be tested.

H. Reduced Pressure Zone Backflow Prevention Device (RPZ): An assembly of check valves and a reduced pressure zone which spills water to the atmosphere in the event of the failure of the check valves. It has valves and fittings which allow the device to be tested, and is referred to as a "testable" device by the District. It requires permitting by the Department.

I. Approved device: A backflow prevention device as approved by the Dept. of Human Services, Division of Health Engineering.

D. Back-siphonage: Backflow resulting from negative or less than atmospheric pressure in the water system.

E. Back-pressure: A condition in which the customer’s system pressure is greater than the supplier's system pressure.


F. Containment: A method of backflow prevention which requires a backflow Prevention Device (containment device) at the water service entrance.

G. Containment device: An approved backflow assembly that may include a strainer as recommended by the manufacturer.

H. Contaminant: Any chemical, biological, or radiological substance or matter which is an impairment of the water quality which creates an actual hazard to the public health through poisoning or through the spread of disease by sewage, industrial fluids, or waste.

I. Cross-Connection: A cross-connection is any connection or arrangement, physical or otherwise, between a potable water supply system and any plumbing fixture, tank, or any receptacle, through which it may be possible for non-potable, used, unclean, polluted, contaminated water, and/or other substances to enter into any part of such potable water system under any condition. It is not necessary for contamination or backflow to have actually occurred. A cross-connection is simply the connection through which it may be possible for backflow or contamination to occur.

J. Cross-connection Survey: An inspection conducted by the District in order to identify any actual or potential
cross-connections, to determine the degree of hazard or potential hazard and appropriate means of backflow prevention, or to confirm compliance with the District's Cross-Connection Program.

K. Customer: A person, firm, corporation, or governmental division which has applied for and been granted service, and is responsible for payment of the service.

L. Department: Maine Department of Health and Human Services

M. District: Winterport Water District

N. Domestic service: A water line which supplies potable water for non-fire protection uses such as drinking, bathing, culinary, heating, and process water purposes.

O. Fire service: A water line which supplies water for fire protection to a fire sprinkler or life safety system.

P. Fixture isolation: A method of backflow prevention in which a backflow prevention device is located to correct a cross-connection in any in-plant unit rather than at the water service entrance. Fixture isolation alone is not deemed an acceptable method of backflow prevention by the District within its distribution system.

Q. Industrial Fluids: Any fluid or solution which may be chemically, biologically or otherwise contaminated or polluted in a form or concentration such as would constitute a health, system, pollutional, or plumbing hazard if introduced into the water supply. This may include but is not limited to :

# polluted or contaminated used waters
# all types of process waters and “used waters” originating from public potable water systems which may # # # deteriorate in
# sanitary quality
# chemicals in fluid form
# plating acids and alkalies
# circulated cooling waters connected to an open cooling tower
# cooling waters that are chemically or biologically treated or stabilized
# contaminated natural waters such as from wells, springs, streams, rivers, etc. or from irrigation systems or canals
# oils, gases, glycerine, paraffines, caustic, and acid solutions or other liquid/gaseous fluids used in industrial or
# other processes solutions used for fire fighting purposes or systems

R. Owner: One in whom the legal title to real estate is vested, or who is recognized and held responsible by law as the Owner of real property.

S. Permit: A document issued by the Department with the approval of the District which requires the use of a specified backflow Prevention Device based on degree of hazard. A cross-connection permit application must be completed by the District and submitted to the Department.

T. Person: Any individual or entity including, without limitation, a partnership, company, public or private corporation, association, political subdivision or agency of the State, Department, Agency, or instrumentality of the United States.

U. Plumbing System: All potable water supply and distribution pipes, all plumbing fixtures and traps, all drainage and vent pipes, and all building drains, including their respective joints and connections, devices, receptacles and appurtenances within the property lines of the premises and shall include potable water piping, potable water treating or using equipment, and water heater.

V. Seasonal Meter Set: A meter which is set for a limited amount of time (such as for the summer) for a specific purpose (such as a swimming pool or fountain).

W. Water Service Entrance: That point in the Customer’s water system beyond the sanitary control of the District. This will normally be the outlet end of the meter and will always be before any unprotected branch.


 

CONTACT WWD | SEARCH | LINKS | LEGAL DISCLAIMER | SITE MAP | HOME